Modbus
Reg.
No.
Description
Modbus
access
Unit
Scaling
factor
On/Off text
or value range
Data / parameter
40342
Output frequency
R
Hz
100
- 327.68 … 327.67 r0024
40343
Output voltage
R
V
1
0 … 32767
r0025
40344
DC-link voltage
R
V
1
0 … 32767
r0026
40345
Actual current value
R
A
100
0 … 163.83
r0027
40346
Actual torque value
R
Nm
100
- 325.00 … 325.00 r0031
40347
Actual active power
R
kW
100
0 … 327.67
r0032
40348
Energy consumption
R
kWh
1
0 … 32767
r0039
40349
Control priority
R
--
1
MANUAL AUTO r0807
Fault diagnostics
40400
Fault number, index 0
R
--
1
0 … 32767
r0947 [0]
40401
Fault number, index 1
R
--
1
0 … 32767
r0947 [1]
40402
Fault number, index 2
R
--
1
0 … 32767
r0947 [2]
40403
Fault number, index 2
R
--
1
0 … 32767
r0947 [3]
40404
Fault number, index 3
R
--
1
0 … 32767
r0947 [4]
40405
Fault number, index 4
R
--
1
0 … 32767
r0947 [5]
40406
Fault number, index 5
R
--
1
0 … 32767
r0947 [6]
40407
Fault number, index 6
R
--
1
0 … 32767
r0947 [7]
40408
Alarm number
R
--
1
0 …32767
r2110 [0]
40499
PRM ERROR code
R
--
1
0 …99
--
Technology controller
40500
Technology controller enable
R/W
--
1
0 … 1
p2200, r2349.0
40501
Technology controller MOP
R/W
%
100
-200.0 … 200.0
p2240
Technology controller adjustment
40510
Time constant for actual-value filters of
the technology controller
R/W
--
100
0.00 … 60.0
p2265
40511
Scaling factor for actual value of the
technology controller
R/W
%
100
0.00 … 500.00
p2269
40512
Proportional amplification of the tech-
nology controller
R/W
--
1000
0.000 … 65.000 p2280
40513
Integral time of the technology control-
ler
R/W
s
1
0 … 60
p2285
40514
Time constant D-component of the
technology controller
R/W
--
1
0 … 60
p2274
40515
Max. limit of technology controller
R/W
%
100
-200.0 … 200.0
p2291
40516
Min. limit technology controller
R/W
%
100
-200.0 … 200.0
p2292
PID diagnostics
40520
Effective setpoint acc. to internal tech-
nology controller MOP ramp-function
generator
R
%
100
-100.0 … 100.0
r2250
40521
Actual value of technology controller
after filter
R
%
100
-100.0 … 100.0
r2266
40522
Output signal technology controller
R
%
100
-100.0 … 100.0
r2294
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......