Functions
7.2 Inverter control
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
337
Five different methods are available for controlling the motor via digital inputs.
Table 7- 1
Two-wire control and three-wire control
Behavior of the motor
Control commands
Typical applica-
tion
Two-wire control, method 1
1.
Switch the motor on and off
(ON/OFF1).
2.
Reverse the motor direction of rota-
tion.
Local control in
conveyor sys-
tems.
Two-wire control, method 2 and
two-wire control, method 3
1.
Switch the motor on and off
(ON/OFF1), clockwise rotation.
2.
Switch the motor on and off
(ON/OFF1), counter-clockwise rota-
tion.
Traction drives
with control via
joystick
Three-wire control, method 1
1.
Enable signal for switching the motor
on and off (OFF1).
2.
Switch the motor on (ON), clockwise
rotation.
3.
Switch the motor on (ON), counter-
clockwise rotation.
Traction drives
with control via
joystick
Three-wire control, method 2
1.
Enable signal for switching the motor
on and off (OFF1).
2.
Switch the motor on (ON).
3.
Reverse the motor direction of rota-
tion.
-
Note
Reversing is disabled in the factory setting. To use the "Reverse" function, you must release
the negative rotational direction, see Section Enable direction of rotation (Page 350).
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......