Alarms, faults and system messages
9.4 Faults
Inverter cabinet units
444
Operating Instructions, 12/2014, A5E32923362A
Extended settings for faults
Parameter
Description
You can change the fault response of the motor for up to 20 different fault codes:
p2100
Setting the fault number for fault response
Selection of the faults for which the fault response applies
p2101
Setting the fault response
Setting the fault response for the selected fault
You can change the acknowledgement type for up to 20 different fault codes:
p2126
Setting the fault number for the acknowledgement mode
Selection of the faults for which the acknowledgement type should be changed
p2127
Setting, acknowledgement mode
Setting the acknowledgement type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgement after removing the fault cause
You can change up to 20 different faults into an alarm or suppress faults:
p2118
Setting the message number for the message type
Selection of the message for which the message type should be changed
p2119
Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
You will find details in function diagram 8075 and in the parameter description of the List
Manual.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......