Operation
6.2 Basic information about the drive system
Inverter cabinet units
174
Operating Instructions, 12/2014, A5E32923362A
Function diagram
FP 8560
Command data sets (CDS)
FP 8565
Drive data sets (DDS)
Parameter
•
p0170
Number of command data sets (CDS)
•
p0180
Number of drive data sets (DDS)
•
p0809[0...2]
Copy command data set CDS
•
p0810
BI: Command data set selection CDS bit 0
•
p0811
BI: Command data set selection CDS bit 1
•
p0819[0...2]
Copy drive data set DDS
•
p0820
BI: Drive data set selection, bit 0
•
p0821
BI: Drive data set selection, bit 1
6.2.3
BICO technology: Interconnecting signals
Description
Every drive contains a large number of interconnectable input and output variables and
internal control variables.
BICO technology (Binector Connector Technology) allows the drive to be adapted to a wide
variety of conditions.
Digital signals, which can be connected freely by means of BICO parameters, are identified
by the prefix BI, BO, CI or CO in their parameter name. These parameters are identified
accordingly in the parameter list or in the function diagrams.
Note
Using STARTER
The STARTER parameterization and commissioning tool is recommended when using BICO
technology.
Binectors, BI: Binector input, BO: Binector output
A binector is a digital (binary) signal without a unit which can assume the value 0 or 1.
Binectors are subdivided into binector inputs (signal sink) and binector outputs (signal
source).
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......