Functions
7.2 Inverter control
Inverter cabinet units
340
Operating Instructions, 12/2014, A5E32923362A
7.2.4
Two-wire control, method 3
You switch the motor on and off using a control command (ON/OFF1) and at the same time
select clockwise motor rotation. You also use the other control command to switch the motor
on and off, but in this case you select counter-clockwise rotation for the motor.
Unlike method 2, the inverter will accept the control commands at any time, regardless of the
motor speed.
Figure 7-4
Two-wire control, method 3
Table 7- 4
Function table
ON/OFF1 clockwise
rotation
ON/OFF1 counter-
clockwise rotation
Function
0
0
OFF1: The motor stops.
1
0
ON: Clockwise motor rotation.
0
1
ON: Counter-clockwise motor rotation.
1
1
OFF1: The motor stops.
Parameter
Description
p0015 = 18
Macro drive unit
Controlling the motor using the digital
inputs of the inverter:
DI 0
DI 1
ON/OFF1 clock-
wise rotation
ON/OFF1 coun-
ter-clockwise
rotation
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p3330[0 … n] = 722.x BI: 2/3 wire control command 1 (ON/OFF1 clockwise rotation)
p3331[0 … n] = 722.x BI: 2/3 wire control command 2 (ON/OFF1 counter-clockwise rotation)
Example
p3331[0 … n] = 722.2 DI 2: ON/OFF1 counter-clockwise rotation
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......