Binary value Objects
Instance
ID
Object name
Description
Possible values Text active Text
inactive
Access
type
Parameter
BV0
RUN/
STOP ACT
Inverter status regardless of
command source
RUN / STOP
STOP
RUN
R
r0052.2
BV1
FWD / REV
Direction of rotation regard-
less of command source
REV / FWD
FWD
REV
R
r0052.14
BV2
FAULT ACT
Inverter fault
FAULT / OK
FAULT
OK
R
r0052.3
BV3
WARN ACT
Inverter warning
WARN / OK
WARN
OK
R
r0052.7
BV4
MANUAL/
AUTO ACT
Indicates the source of the
manual/auto inverter control
AUTO /
MANUAL
AUTO
LOCAL
R
r0052.9
BV7
CTL
OVERRIDE
ACT
ACT displays the inverter's
control from the BACnet over-
ride control via BV93.
Note that the operator panel's
"Manual" operating mode has
a higher priority than the
BACnet override control.
ON/OFF
0
1
R
r2032[10]
BV8
AT SET-
POINT
Setpoint reached
YES / NO
YES
NO
R
r0052.8
BV9
AT MAX
FREQ
Maximum speed reached
YES / NO
YES
NO
R
r0052.10
BV10
DRIVE
READY
Inverter ready
YES / NO
YES
NO
R
r0052.1
BV15
RUN COM
ACT
ACT indicates the status of
the ON command, regardless
of the source
YES / NO
0
1
R
r2032[0]
BV16
HIB MOD ACT ACT means that the inverter
is operating in energy-saving
mode
ON/OFF
0
1
R
r2399[1]
BV17
ESM MOD
ACT means that the inverter
is operating in the essential
service mode
ON/OFF
0
1
R
r3889[0]
BV20
RUN/
STOP CMD
ON command for the inverter
(when controlling via BACnet)
RUN / STOP
0
1
C
r0054.0
BV21
FWD/
REV CMD
Reverse direction of rotation
(when controlling via BACnet)
REV / FWD
0
1
C
r0054.11
BV22
FAULT
RESET
Acknowledge fault (when
controlling via BACnet)
RESET / NO
0
1
C
r0054.7
BV24
CDS
Local / Remote
Local / Remote YES
NO
C
r0054.15
BV26
RUN ENA
CMD
Enable inverter operation
ENABLED DISABLED C
r0054.3
BV27
OFF2
OFF2 status
RUN / STOP
0
1
C
r0054.1
BV28
OFF3
OFF3 status
Note:
BV28 sets the r0054.4,
r0054.5, and r0054.6 bits
RUN / STOP
0
1
C
r0054.2
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......