Commissioning
5.3 Commissioning with the IOP
Inverter cabinet units
140
Operating Instructions, 12/2014, A5E32923362A
20. Select the minimum speed for the connected motor.
Individual digits or the complete value can be changed.
Change the input mode by pressing the navigation
wheel for a longer time.
21. Specify the ramp-up time.
In this time, the speed setpoint of the ramp-function
generator is increased from standstill to the maximum
speed (p1082).
Individual digits or the complete value can be changed.
Change the input mode by pressing the navigation
wheel for a longer time.
22. Specify the ramp-down time.
In this time, the speed setpoint of the ramp-function
generator is decreased from the maximum speed
(p1082) to standstill.
The ramp-down time always acts for an OFF1 com-
mand.
Individual digits or the complete value can be changed.
Change the input mode by pressing the navigation
wheel for a longer time.
23. Select the type of the motor temperature sensor.
24. Select the cabinet options:
•
Line filter (L00)
•
Line harmonics filter (L01)
•
dv/dt filter (L07)
•
Motor reactor (L08)
•
dv/dt filter plus VPL (L10)
•
Without line reactor (L22)
•
EMERGENCY OFF button (L45)
•
EMERGENCY OFF Cat 0 (L57)
•
EMERGENCY OFF Cat 1 (L59)
•
EMERGENCY OFF Cat 1 24 V (L60)
•
Braking Mod. 25 kW (L61)
•
Braking Mod. 50 kW (L62)
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......