Operation
6.8 Communication via RS485
Inverter cabinet units
240
Operating Instructions, 12/2014, A5E32923362A
Communication error
If the slave detects a communication error on receipt (parity, CRC), it does not send a
response to the master (this can lead to "setpoint timeout").
Logical error
If the slave detects a logical error within a request, it responds to the master with an
"exception response". In this case, the slave sets the highest bit in the function code to 1 in
the response. If, for example, it receives an unsupported function code from the master, the
slave responds with an "exception response" with code 01 (illegal function code).
Table 6- 28 Overview of exception codes
Exception
code
Modbus name
Remark
01
Illegal function code
An unknown (unsupported) function code was sent to the
slave.
02
Illegal Data Address
An invalid address was requested.
03
Illegal data value
An invalid data value was detected.
04
Server failure
Slave has terminated during processing.
Maximum processing time, p2024[0]
The slave-response time is the time in which the Modbus master expects a response to a
request. Set the same slave-response time (p2024 [0] in the inverter) in the master and
slave.
Process data monitoring time (setpoint timeout), p2040
"Setpoint timeout" (F1910) is issued by the Modbus if p2040 is set to a value > 0 ms and no
process data is requested within this time period.
The "Setpoint timeout" only applies for access to process data (40100, 40101, 40110,
40111). The "Setpoint timeout" is not generated for parameter data (40200 … 40522).
Note
Adjust the time (factory setting = 100 ms) depending on the number of slaves and the baud
rate set on the bus.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......