Operation
6.5 PROFIdrive profile for PROFIBUS and PROFINET
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
193
Procedure
Proceed as follows to extend a telegram:
1.
Use STARTER or the IOP to set parameter p0922 = 999.
2.
Set parameter p2079 to the appropriate value of the corresponding telegram.
3.
Interconnect additional PZD send words and PZD receive words with signals of your
choice via parameters r2050 and p2051.
Parameter
Description
p0922
PROFIdrive telegram selection
999: Free telegram (message frame) configuration
p2079
PROFIdrive PZD telegram selection extended
1:
20:
350:
352:
353:
354:
Standard telegram 1, PZD-2/2
Standard telegram 20, PZD-2/6
SIEMENS telegram 350, PZD-4/4
SIEMENS telegram 352, PZD-6/6
SIEMENS telegram 353, PZD-2/2, PKW-4/4
SIEMENS telegram 354, PZD-6/6, PKW-4/4
r2050[0…11] PROFIdrive PZD receive word
Connector output to interconnect the PZD (setpoints) in the word format received
from the PROFIdrive controller.
p2051[0…11] PROFIdrive PZD send word
Selection of the PZD (actual values) in the word format to be sent to the PROFIdrive
controller.
Selection of the PZD (actual values) in the word format to be sent to the PROFIdrive
controller. For further information refer to the function block diagrams 2468 and 2470 of the
List Manual.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......