Alarms, faults and system messages
9.5 List of alarms and faults
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
449
Number Cause
Remedy
A07921
Torque/speed too high
•
Check the connection between the motor and the load.
•
Adapt the parameterization corresponding to the load.
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
•
Check the connection between the motor and the load.
•
Adapt the parameterization corresponding to the load.
F07924
Torque/speed too high
A07927
DC braking active
Not required
A07980
Rotary measurement activated
Not required
A07981
No enabling for rotary measure-
ment
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
A07991
Motor identification activated
Switch on the motor and identify the motor data.
F08501
PROFINET: Setpoint timeout
•
Check the PROFINET connection.
•
Set the controller into the RUN mode.
•
If the fault occurs repeatedly, check the monitoring time set p2044.
F08502
PROFINET: Monitoring time, sign-
of-life expired
•
Check the PROFINET connection.
F08510
PROFINET: Send configuration
data not valid
•
Check the PROFINET configuration
A08511
PROFINET: Receive configuration
data not valid
A08526
PROFINET: No cyclic connection
•
Activate the controller with cyclic operation.
•
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565
PROFINET: Consistency error
affecting adjustable parameters
Check the following:
•
IP address, subnet mask or default gateway is not correct.
•
IP address or station name used twice in the network.
•
Station name contains invalid characters.
F08700
CAN: Communications error
A CAN communications error has occurred. Check the following:
•
Bus cable
•
Baud rate (p8622)
•
Bit timing (p8623)
•
Master
Start the CAN controller manually with p8608 = 1 after the cause of the
fault has been resolved!
A8800
PROFIenergy energy-saving mode
active
Not required
F13100
Know-how protection: Copy protec-
tion error
The know-how protection and the copy protection for the memory card
are active. An error occurred when checking the memory card.
•
Insert a suitable memory card and switch the inverter supply voltage
temporarily off and then on again (POWER ON).
•
Deactivate the copy protection (p7765).
F13101
Know-how protection: Copy protec-
tion cannot be activated
Insert a valid memory card.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......