Operation
6.9 Communication over CANopen
Inverter cabinet units
272
Operating Instructions, 12/2014, A5E32923362A
Interconnecting process data via a free PDO mapping
Procedure
To interconnect process data, proceed as follows:
1.
Define process data,
examples:
–
Send actual current value (r0068) from the inverter to the controller (TPDO - Transmit
Process Data Object)
–
Send additional speed setpoint from the controller to the inverter (RPDO - Receive
Process Data Object) and write in p1075
2.
Specify objects for transmission of the process data
–
TPDO1 for the actual current value
–
RPDO1 for additional speed setpoint
3.
Set communication parameters for RPDO and TPDO
–
Define the communication parameters for RPDO, see RPDO communication
parameters (Page 278)
–
Define the communication parameters for TPDO, see TPDO communication
parameters (Page 282)
4.
Select the OD index for the mapping parameters:
–
Mapping parameters for RPDO, see RPDO mapping parameters (Page 279)
–
Mapping parameters for TPDO, see TPDO mapping parameters (Page 283)
5.
Write OV index into the SINAMICS mapping parameters
–
p8710 … p8717 for RPDO
–
p8730 … p8737 for TPDO
–
You will find the OD index in the free objects (Page 286) or in the objects of the CiA
402 drive profile (Page 276)
Note
Requirement for changing the OD indexes of the SINAMICS mapping parameters
To allow you to change the values of the mapping parameters, you must set the COB ID of
the corresponding parameter to invalid. Add the value 80000000 hex to the COB ID. If you
have changed the mapping parameter, you must reset the COB ID to the valid value.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......