Technical specifications
11.3 Technical specifications
Inverter cabinet units
480
Operating Instructions, 12/2014, A5E32923362A
Article number
6SL3710- 1PE33-7AA0
1PE34-6AA0
1PE35-8AA0
- non-compliant with the limit values for
interference and with output choke or
dv/dt filter, shielded/unshielded
m
300/450
300/450
300/450
Dimensions (standard version)
- Width
- Height
- Depth
mm
mm
mm
1000
2000
8)
600
1000
2000
8)
600
1200
2000
9)
600
Power Module frame size
GX
GX
HX
Weight (without options), approx.
kg
380
400
500
Recommended protection
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor protection
(without option L26)
Rated current
Frame size to IEC 60269
A
A
3NA3365
500
3
3NE1334-2
500
2
3NA3372
630
3
3NE1435-2
560
3
3NA3372
630
3
3NE1437-2
710
3
Short-circuit current rating according to
IEC
10)
kA
65
65
65
Minimum short-circuit current
11)
- For 3NE1 fuses
- For 3NA3 fuses
A
A
5200
14000
6300
20000
9000
20000
1)
Rated output of a typical 4-pole standard induction motor based on I
L
or I
H
at 3-phase 400 V AC 50 Hz.
2)
Rated output of a typical 4-pole standard induction motor based on I
L
or I
H
at 3-phase 460 V AC 60 Hz.
3)
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 135% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
4)
The base-load current I
H
is based on a duty cycle of 150% for 60 s with a duty cycle duration of 300 s (see "Overload
capability").
5)
The current values given here are based on the rated output current.
6)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC (National
Electrical Code) or CEC (Canadian Electrical Code) standards.
7)
The connecting blocks can be damaged when using longer screws.
8)
The cabinet height increases by 300 mm for IP20 and IP21 degrees of protection, and by 400 mm for IP23, IP43 and IP54
degrees of protection.
9)
The cabinet height increases by 300 mm for IP21 degree of protection, and by 400 mm for IP23, IP43 and IP54 degrees
of protection.
10)
In conjunction with the specified fuses or circuit breakers.
11)
Minimum current required for a reliable activation of the designated protection devices.
Caution: If the minimum short circuit current is not reached, the rupture time of the fuses is increased, which can lead to
damage.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......