Operation
6.8 Communication via RS485
Inverter cabinet units
246
Operating Instructions, 12/2014, A5E32923362A
Object property
Object type
Binary Input
Binary
Output
Binary Value Analog Input
Analog
Output
Analog
Value
Multi-State
Input
Inactive_Text
X
X
X
COV_Increment
X
X
X
State_Text
X
Number_of_States
X
* for command values only (access type C)
Note
Access types are available in the following versions:
•
C: Executable
•
R: Readable
•
W: Writable
Binary Input Objects
Instance
ID
Object name
Description
Possible
values
Text active /
text inactive
Access
type
Parameter
BI0
DI0 ACT
State of DI 0
ON/OFF
ON/OFF
R
r0722.0
BI1
DI1 ACT
State of DI 1
ON/OFF
ON/OFF
R
r0722.1
BI2
DI2 ACT
State of DI 2
ON/OFF
ON/OFF
R
r0722.2
BI3
DI3 ACT
State of DI 3
ON/OFF
ON/OFF
R
r0722.3
BI4
DI4 ACT
State of DI 4
ON/OFF
ON/OFF
R
r0722.4
BI5
DI5 ACT
State of DI 5
ON/OFF
ON/OFF
R
r0722.5
BI7
DI7 ACT
State of AI 1 - used as DI
ON/OFF
ON/OFF
R
r0722.11
BI8
DI8 ACT
State of AI 2 - used as DI
ON/OFF
ON/OFF
R
r0722.12
BI10
DO0 ACT
State of DO 0 (relay 1)
ON/OFF
ON/OFF
R
read r747.0
BI11
DO1 ACT
State of DO 1 (relay 2)
ON/OFF
ON/OFF
R
read r747.1
BI12
DO2 ACT
State of DO2 (relay 3)
ON/OFF
ON/OFF
R
read r747.2
Binary Output Objects
Instance
ID
Object name
Description
Possible
values
Text active /
text inactive
Access
type
Parameter
BO0
DO0 CMD
Controls DO 0 (relay 1)
ON/OFF
ON/OFF
C
p0730
BO1
DO1 CMD
Controls DO 1 (relay 2)
ON/OFF
ON/OFF
C
p0731
BO2
DO2 CMD
Controls DO 2 (relay 3)
ON/OFF
ON/OFF
C
p0732
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......