Functions
7.2 Inverter control
Inverter cabinet units
338
Operating Instructions, 12/2014, A5E32923362A
7.2.2
Two-wire control, method 1
You switch the motor on and off using a control command (ON/OFF1) while the other control
command reverses the motor direction of rotation.
Figure 7-2
Two-wire control, method 1
Table 7- 2
Function table
ON/OFF1
Reversing
Function
0
0
OFF1: The motor stops.
0
1
OFF1: The motor stops.
1
0
ON: Clockwise motor rotation.
1
1
ON: Counter-clockwise motor rotation.
Parameter
Description
p0015 = 12
Drive unit macro (factory setting for inverters with CU230P-2 HVAC and
CU230P-2 CAN)
Controlling the motor using the digital inputs
of the inverter:
DI 0
DI 1
ON/OFF1
Reversing
Advanced setting
Interconnecting control commands with digital inputs of your choice (DI x).
p0840[0 … n] = 722.x BI: ON/OFF1 (ON/OFF1)
p0841[0 … n] = 722.x BI: Setpoint inversion (reversing)
Example
p3330[0 … n] = 722.3 DI 3: ON/OFF1