Functions
7.4 Setpoint calculation
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
351
7.4.5
Skip frequency bands
The inverter prevents continuous motor operation
at speeds in the suppression-speed range.
This can prevent speeds from being approached
stationary that, for example, cause excitation of
resonancy vibrations of the drive train.
To ensure that the speed does not constantly
increase and decrease in the suppression band-
width (speeds), the bands are assigned a hyste-
resis.
The suppression speeds apply in the positive and
negative direction of rotation.
Table 7- 18 Setting skip frequency bands
Parameter
Description
p1091
Suppression speed 1
p1092
Suppression speed 2
p1093
Suppression speed 3
p1094
Suppression speed 4
p1098
Suppression speed scaling
p1101
Suppression speed bandwidth