Technical specifications
11.3 Technical specifications
Inverter cabinet units
484
Operating Instructions, 12/2014, A5E32923362A
Article number
6SL3710- 1PE32-1CA0
1PE32-5CA0
1PE33-0CA0
Dimensions (standard version)
- Width
- Height
8)
- Depth
mm
mm
mm
600
2000
600
600
2000
600
600
2000
600
Power Module frame size
GX
GX
GX
Weight (without options), approx.
kg
290
290
290
Recommended protection
- Line protection
(with option L26)
Rated current
frame size to IEC 60269
- Line and semiconductor protection
(without option L26)
Rated current
Frame size to IEC 60269
A
A
3NA3144
250
1
3NE1230-2
315
1
3NA3252
315
2
3NE1331-2
350
2
3NA3260
400
2
3NE1333-2
450
2
Short-circuit current rating according to
IEC
9)
kA
65
65
65
Minimum short-circuit current
10)
- For 3NE1 fuses
- For 3NA3 fuses
A
A
3000
5800
3600
7300
4400
9500
1)
Rated output of a typical 4-pole standard induction motor based on I
L
or I
H
at 3-phase 400 V AC 50 Hz.
2)
Rated output of a typical 4-pole standard induction motor based on I
L
or I
H
at 3-phase 460 V AC 60 Hz.
3)
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 135% for 3 s with a duty cycle duration of 300 s (see
"Overload capability").
4)
The base-load current I
H
is based on a duty cycle of 150% for 60 s with a duty cycle duration of 300 s (see "Overload
capability").
5)
The current values given here are based on the rated output current.
6)
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC (National
Electrical Code) or CEC (Canadian Electrical Code) standards.
7)
The connecting blocks can be damaged when using longer screws.
8)
The cabinet height increases by 300 mm for IP21 degree of protection, and by 400 mm for IP23, IP43 and IP54 degrees
of protection.
9)
In conjunction with the specified fuse elements.
10)
Minimum current required for reliable activation of the designated protection devices.
Caution: If the minimum short circuit current is not reached, the rupture time of the fuses is increased, which can lead to
damage.
Summary of Contents for SINAMICS G120P