Operation
6.5 PROFIdrive profile for PROFIBUS and PROFINET
Inverter cabinet units
192
Operating Instructions, 12/2014, A5E32923362A
Status word 3 (ZSW3)
Status word 3 has the following standard assignment. See also function diagram 2456.
Bit Value Significance
Description
Signal interconnection
in the inverter
0 1
DC braking active
--
p2051[3] = r0053
1 1
|n_act| > p1226
Absolute actual speed > stationary state
detection
2 1
|n_act| > p1080
Absolute actual speed > minimum speed
3 1
i_act
≧ p2170
Actual current ≥ current threshold value
4 1
|n_act| > p2155
Absolute actual speed > speed threshold
value 2
5 1
|n_act| ≦ p2155
Absolute actual speed < speed threshold
value 2
6 1
|n_act| ≧ r1119
Speed setpoint reached
7 1
DC-link voltage
≦ p2172
Actual DC-
link voltage ≦ threshold value
8 1
DC-link voltage > p2172
Actual DC-link voltage > threshold value
9 1
Ramping completed
Ramp-function generator is not active.
10 1
Technology controller output at lower limit Technology controller
output ≦ p2292
11 1
Technology controller output at upper limit Technology controller output > p2291
12
Reserved
13
Reserved
14
Reserved
15
Reserved
6.5.1.3
Extend telegrams and change signal interconnection
When you have selected a telegram, the inverter interconnects the corresponding signals
with the fieldbus interface. Generally, these interconnections are protected so that they
cannot be changed. With the appropriate inverter settings, these interconnections can be
changed.
Extending a telegram
Every telegram can be extended by "attaching" additional signals.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......