Electrical installation
4.8 Signal connections
Inverter cabinet units
92
Operating Instructions, 12/2014, A5E32923362A
Motor temperature sensor interface
Table 4- 24 Motor temperature sensor interface
Pin
Designation
Technical data
14
T1 MOTOR
Positive input for motor temperature sensor
Type: PTC, KTY sensor, Thermo-Click
15
T2 MOTOR
Negative input for motor temperature sensor
Max. connectable cross-section: 1.5 mm²
Power supply
Table 4- 25 Power supply
Pin
Designation
1)
Technical data
9
+24 V OUT
Power supply output
24 VDC, max. 200 mA
28
GND
Reference potential of the power supply/internal electronics ground
1
+10 V OUT
Power supply output
10 VDC ±0.5 V, max. 10 mA
2
GND
Reference potential of the power supply/internal electronics ground
31
+24 V IN
Power supply input
18 ... 30 VDC, max. 1500 mA
32
GND IN
Reference potential of the power supply input
35
+10 V OUT
Power supply output
10 VDC ±0.5 V, max. 10 mA
36
GND
Reference potential of the power supply/internal electronics ground
Max. connectable cross-section: 1.5 mm²
1)
GND: reference potential
X128: Serial interface (RS485)
Table 4- 26 Serial interface (RS485) X128
Terminal
Designation
Technical data
1
0 V
Ground reference
2
RS485P
Receive and tr
3
RS485N
Receive and transmit -
4
GND
Cable shield
5
--
not used
Max. connectable cross-section: 1.5 mm²
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...