Operation
6.2 Basic information about the drive system
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
177
Example 1: interconnecting digital signals
Suppose you want to operate a drive via terminals DI 0 and DI 1 on the Control Unit using
jog 1 and jog 2.
Figure 6-4
Interconnection of digital signals (example)
Binector-connector converters and connector-binector converters
Binector-connector converter
●
Several digital signals are converted to a 32-bit integer double word or to a 16-bit integer
word.
●
p2080[0...15] BI: Binector-connector converter, status word 1
●
p2081[0...15] BI: Binector-connector converter, status word 2
●
p2082[0...15] BI: Binector-connector converter, status word 3
●
p2083[0...15] BI: Binector-connector converter, status word 4
●
p2084[0...15] BI: Binector-connector converter, status word 5
Connector-binector converter
●
A 32-bit integer double word or a 16-bit integer word is converted to individual digital
signals.
●
p2099[0...1] CI: Connector-binector converter signal source
Fixed values for interconnection using BICO technology
The following connector outputs are available for interconnecting any fixed value settings:
•
p2900[0...n]
CO: Fixed value 1[%]
•
p2901[0...n]
CO: Fixed value 2[%]
•
p2930[0...n]
CO: Fixed value M [Nm]
Example:
These parameters can be used to interconnect the scaling factor for the main setpoint or to
interconnect an additional torque.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......