Functions
7.6 Protection functions
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
367
Setting parameters for the temperature monitoring
Parameter
Description
p0335
Specify the motor cooling
0: Natural cooling - with fan on the motor shaft (factory setting)
1: Forced ventilation - with a separately driven fan
2: Liquid cooling
128: No fan
p0601
Motor-temperature sensor type
0: No sensor (factory setting)
1: PTC (
→ p0604)
2: KTY84 (→ p0604, p0605)
4: Temperature switch
p0604
Motor temperature alarm threshold (factory setting 130° C)
p0605
Motor temperature fault threshold (factory setting 145° C)
Setting for KTY84 sensor. The parameter has no significance for a PTC sensor.
p0610
Motor overtemperature response
Determines the response when the motor temperature reaches the alarm threshold
p0604.
0: Alarm (A07910), no fault.
1: Alarm (A07910); current limit is reduced and timer is started. Shutdown with fault
(F07011).
2: Alarm (A07910); timer is started. Shutdown with fault (F07011).
12: As for 2 but the last shutdown temperature is used to calculate the motor temper-
ature (factory setting).
p0640
Current limit (input in A)
Additional information on the motor temperature monitoring can be found in function diagram
8016 of the List Manual.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......