Functions
7.7 Application-specific functions
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
419
Activating the hibernation mode with setpoint input via the internal technology controller
With this operating mode you have to set the technology closed-loop controller as the
setpoint source (p2200) and use the output of the technology closed-loop controller as the
main setpoint (p2251). The boost can be deactivated.
Figure 7-31 Hibernation mode using the technology setpoint as main setpoint with boost