Functions
7.7 Application-specific functions
Inverter cabinet units
408
Operating Instructions, 12/2014, A5E32923362A
7.7.15
Cascade control
Cascade control is suitable for applications that require simultaneous operation of up to four
motors as a function of the load. Here, for example, significantly fluctuating pressures or flow
rates are equalized.
Depending on the PID variance, the inverter's cascade control switches up to three other
motors on or off via contactors or motor starters.
Note
Technology closed-loop controller as main setpoint
For cascade control switch the main setpoint with the output of the technology closed-loop
controller (p2251 = 0, p2200 =1)
Note
In STARTER, the function is called "Motor staging".
Operating principle
●
Connecting external motors
If the main drive is run at maximum speed and the deviation on the technology closed-
loop controller input continues to increase, the controller also switches the external
motors on the line system. At the same time, the main drive is ramped down to the
switch-on/switch-off speed (p2378) to keep the total output power as constant as
possible. The technology closed-loop controller is deactivated while ramping down to the
switch-on/switch-off speed.
●
Disconnecting external motors
If the main drive is running at minimum speed and the deviation on the technology
closed-loop controller input continues to decrease, the controller disconnects the external
motors M1 to M3 from the line system. The main drive is simultaneously ramped-up to the
switch-on/switch-off speed to keep the total output power as constant as possible.
To avoid frequent activation/deactivation of the uncontrolled motors, you must specify a time
in p2377 which must have elapsed before the inverter can switch a further motor on or off.
After the time set in p2377 has elapsed, a further motor will be activated immediately if the
PID deviation is greater than the value set in p2376. If, after p2377 has elapsed, the PID
deviation is less than p2376 but greater than 2373, the timer p2374 is started before the
uncontrolled motor is activated.
The motors are deactivated in the same way.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......