Chapter 4
System Administration
RUGGEDCOM ROX II
User Guide
194
Configuring an Alarm
1
2
3
4
5
6
Figure 205: Alarm Configuration Form
1.
Description Box
2.
Severity List
3.
Admin Enable Check Box
4.
Failrelay Enable Check Box
5.
LED Enable Check Box
6.
Auto Clear Check Box
3. Configure the following parameters as required:
Parameter
Description
description
The name of the alarm.
severity
Synopsis:
emergency, alert, critical, error, warning, notice, info, debug
The severity level can be one of emergency, alert, critical, error, warning, notice, info,
and debug. This cannot be changed for some alarms.
admin-enable
If disabled, the alarm is not reported in the active list and does not actuate LED/failrelay.
failrelay-enable
If enabled, this alarm will assert the failrelay.
led-enable
If enabled, the main 'Alarm' LED light will be red when this alarm is asserted. If disabled,
the main 'Alarm' LED light is not affected by this alarm.
auto-clear
If enabled, the LED and failrelay will be cleared automatically when condition is met.
4. Click
Commit
to save the changes or click
Revert All
to abort. A confirmation dialog box appears. Click
OK
to proceed.
5. Click
Exit Transaction
or continue making changes.
Summary of Contents for RUGGEDCOM RX1510
Page 32: ...RUGGEDCOM ROX II User Guide Preface Customer Support xxxii ...
Page 44: ...RUGGEDCOM ROX II User Guide Chapter 1 Introduction User Permissions 12 ...
Page 62: ...RUGGEDCOM ROX II User Guide Chapter 2 Using ROX II Using the Command Line Interface 30 ...
Page 268: ...RUGGEDCOM ROX II User Guide Chapter 4 System Administration Deleting a Scheduled Job 236 ...