HiPath 3000/5000 V9, Service documentation
4-89
Nur für den internen Gebrauch
Installing HiPath 3000
Installing HiPath 3550, HiPath 3350, HiPath 3500, and HiPath 3300
Information on the design can be found in the following sections:
●
●
4.2.3.1.1
For U.S. only: Power plug
The AC connection must fulfill the requirements specified in Table 4-11.
AC Outlet Requirements
●
The power source may not be more than 2 m (6 ft.) from the system.
●
The power source must supply a voltage of 120 V AC (single phase, fused) in 50-60 Hz.
●
A warning should be attached to the circuit breaker to prevent accidental removal of power.
●
An independent electric circuit with an isolated ground conductor should be used.
●
Recommendation: Add a power surge protector between the AC outlet and the system.
Table 4-11
Electrical Connection Values (for U.S. only)
Nominal
voltage
Nominal voltage range
Nominal Frequency
Range
Wall Outlet Configura-
tions
from
to
from to
120 V AC/
60 Hz
110 V AC
130 V AC
47 Hz
63 Hz
NEMA 5-15, 2-pin, 3-
wire, earth