List of Parameters
Parameters
1-193
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the signal source for the lower torque limit.
Dependency:
Refer to: p1520, p1521, p1522
Danger:
Positive values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Description:
Sets the scaling for the upper torque limit or the torque limit when motoring.
Dependency:
p1400 bit 4 = 0: Upper / lower
p1400 bit 4 = 1: Motoring / regenerative
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description:
Sets the scaling for the lower torque limit.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
Description:
Displays the upper torque limit of all torque limits without offset.
Dependency:
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
Description:
Displays the lower torque limit of all torque limits without offset.
Dependency:
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
p1523[0...n]
CI: Torque limit lower / M_max lower
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2003
Data set:
CDS, p0170
Min Max Factory
setting
- - 1521[0]
p1524[0...n]
CO: Torque limit upper/motoring scaling / M_max up/mot scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]
p1525[0...n]
CO: Torque limit lower scaling / M_max lower scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-2000.0 [%]
2000.0 [%]
100.0 [%]
r1526
CO: Torque limit upper without offset / M_max up w/o offs
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Nm]
Scaling:
p2003
Data set:
-
r1527
CO: Torque limit lower without offset / M_max low w/o offs
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[Nm]
Scaling:
p2003
Data set:
-