List of Parameters
Parameters
1-373
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Setting parameter for the run sequence of instance PDF 1 within the run-time group set in p20176.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source for input pulse I and the reset input R of instance PST 0 of the pulse extension element.
Index:
[0] = Input pulse I
[1] = Reset input R
Description:
Setting parameter for pulse duration T in milliseconds of instance PST 0 of the pulse extension element.
Description:
Display parameter for output pulse Q of instance PST 0 of the pulse extension element.
Description:
Setting parameter for the run-time group in which the instance PST 0 of the pulse extension element is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance PST 0 within the run-time group set in p20181.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20177
PDF 1 run sequence / PDF 1 RunSeq
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 32000
470
p20178[0...1]
BI: PST 0 inputs / PST 0 inputs
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
- - 0
p20179
PST 0 pulse duration in ms / PST 0 pulse_dur ms
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 60000.00
0.00
r20180
BO: PST 0 output Q / PST 0 output Q
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
p20181
PST 0 run-time group / PST 0 RTG
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
5 9999
9999
p20182
PST 0 run sequence / PST 0 RunSeq
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 7999
490