List of Parameters
Parameters
1-319
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1600 hex + 40 hex * x (x: Drive number 0 ... 7).
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 2 (RPDO 2).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1601 hex + 40 hex * x (x: Drive number 0 ... 7).
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 3 (RPDO 3).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1602 hex + 40 hex * x (x: Drive number 0 ... 7).
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
p8710[0...3]
CAN Receive Mapping für RPDO 1 / Mapping RPDO 1
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8711[0...3]
CAN Receive Mapping für RPDO 2 / Mapping RPDO 2
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8712[0...3]
CAN Receive Mapping für RPDO 3 / Mapping RPDO 3
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
Summary of Contents for CU230P-2 CAN