List of Parameters
Parameters
1-115
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the send and receive telegram.
Value:
1:
Standard telegram 1, PZD-2/2
20:
Standard telegram 20, PZD-2/6
350:
SIEMENS telegram 350, PZD-4/4
352:
SIEMENS telegram 352, PZD-6/6
353:
SIEMENS telegram 353, PZD-2/2, BW-PKW-4/4
354:
SIEMENS telegram 354, PZD-6/6, BW-PKW-4/4
999:
Free telegram configuration with BICO
Dependency:
Refer to: F01505
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description:
Displays fault buffer changes. This counter is incremented every time the fault buffer changes.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109
Description:
Displays the numbers of faults that have occurred.
Dependency:
Refer to: r0947, r0948, r0949, r2109, r2130, r2133, r2136
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0] --> actual fault case, fault 1
. . .
r0945[7], r0949[7], r0948[7], r2109[7] --> actual fault case, fault 8
r0945[8], r0949[8], r0948[8], r2109[8] --> 1st acknowledged fault case, fault 1
. . .
r0945[15], r0949[15], r0948[15], r2109[15] --> 1st acknowledged fault case, fault 8
. . .
r0945[56], r0949[56], r0948[56], r2109[56] --> 7th acknowledged fault case, fault 1
. . .
r0945[63], r0949[63], r0948[63], r2109[63] --> 7th acknowledged fault case, fault 8
Description:
Lists the fault codes stored in the drive unit.
The indices can only be accessed with a valid fault code.
Dependency:
The parameter assigned to the fault code is entered in r0951 under the same index.
Refer to: r0951
p0922
PROFIdrive telegram selection / PD Telegr_sel
CU230P-2 DP
Access level:
1
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(1), T
Scaling:
-
Data set:
-
Min Max Factory
setting
1 999
1
r0944
CO: Counter for fault buffer changes / Fault buff change
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
r0945[0...63]
Fault code / Fault code
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
r0946[0...65534] Fault code list / Fault code list
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-