List of Parameters
Parameters
1-247
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the fault response for the selected fault.
Value:
0:
NONE
1:
OFF1
2:
OFF2
3:
OFF3
5:
STOP2
6:
IASC/DCBRAKE
Dependency:
The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice:
It is not possible to re-parameterize the response to a specific fault for faults that are already present (queued).
Note:
OFF1:
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
OFF2:
Internal/external pulse inhibit.
OFF3:
Braking along the OFF3 down ramp followed by a pulse inhibit.
STOP2:
n_set = 0
The fault response can only be changed for faults with the appropriate identification.
IASC / DC BRAKE:
a) A DC brake is not possible for synchronous motors.
b) A DC brake is possible for induction motors.
Example:
F12345 and fault response = NONE (OFF1, OFF2) --> The NONE fault response can be changed to either OFF1 or
OFF2.
The value can only be set for all drive data sets when p1231 = 4.
Description:
Sets the first signal source to acknowledge faults.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
Description:
Sets the first signal source to acknowledge faults.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
A fault acknowledgement is triggered with a 0/1 signal.
p2101[0...19]
Setting the fault response / Fault response
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 6 0
p2103[0...n]
BI: 1. Acknowledge faults / 1. Acknowledge
CU230P-2 CAN
CU230P-2 HVAC
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
p2103[0...n]
BI: 1. Acknowledge faults / 1. Acknowledge
CU230P-2 DP
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 2090.7