Parameters
List of Parameters
1-212
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the modulator mode.
Value:
0:
Automatic changeover SVM/FLB
2:
Space vector modulation (SVM)
3:
SVM without overcontrol
4:
SVM/FLB without overcontrol
10:
SVM/FLB with modulation depth reduction
Dependency:
If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without over-
control can be selected as modulation type (p1802 = 3).
Refer to: p0230
Note:
When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2), the modulation depth must
be limited using p1803 (pre-assignment, p1803 = 98%). The higher the overmodulation, the greater the current rip-
ple and torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
Description:
Sets the modulator mode.
Value:
0:
Automatic changeover SVM/FLB
2:
Space vector modulation (SVM)
3:
SVM without overcontrol
4:
SVM/FLB without overcontrol
Dependency:
If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without over-
control can be selected as modulation type (p1802 = 3).
Refer to: p0230
Note:
When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2), the modulation depth must
be limited using p1803 (pre-assignment, p1803 = 98%). The higher the overmodulation, the greater the current rip-
ple and torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
Description:
Defines the maximum modulation depth.
Note:
p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description:
Defines the maximum modulation depth.
Note:
p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
p1802[0...n]
Modulator mode / Modulator mode
PM240
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 10
0
p1802[0...n]
Modulator mode / Modulator mode
PM250
PM260
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 4 4
p1803[0...n]
Maximum modulation depth / Modulat depth max
PM230
Access level:
4
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
20.0 [%]
120.0 [%]
115.0 [%]
p1803[0...n]
Maximum modulation depth / Modulat depth max
PM230
PM250, PM260
Access level:
4
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
20.0 [%]
120.0 [%]
100.0 [%]