List of Parameters
Parameters
1-321
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 7 (RPDO 7).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1606 hex + 40 hex * x (x: Drive number 0 ... 7).
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
Description:
Sets the mapping parameters for CANopen Receive Process Data Object 8 (RPDO 8).
Index:
[0] = Mapped object 1
[1] = Mapped object 2
[2] = Mapped object 3
[3] = Mapped object 4
Note:
Corresponds to the CANopen object 1607 hex + 40 hex * x (x: Drive number 0 ... 7).
Dummy mapping not supported.
The parameter can only be written online when the associated COB ID in p870x is set as invalid.
Description:
Sets the communication parameters for CANopen Transmit Process Data Object 1 (TPDO 1).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Notice:
For inhibit time and even timer, the following apply:
A value that is not a multiple integer of CANopen (4 ms) is rounded-off.
Note:
Corresponds to the CANopen object 1800 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1 ... F0, FE and FF can be set.
PDO: Process Data Object
p8716[0...3]
CAN Receive Mapping für RPDO 7 / Mapping RPDO 7
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8717[0...3]
CAN Receive Mapping für RPDO 8 / Mapping RPDO 8
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
FFFF FFFF hex
0000 hex
p8720[0...4]
CAN Transmit PDO 1 / Transmit PDO 1
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
C000 06DF hex
C000 06DF hex