List of Parameters
Parameters
1-265
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2188 < p2187
Refer to: p2183, p2187
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2189 > p2190
Refer to: p2184, p2190
Refer to: A07926
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2190 < p2189
Refer to: p2184, p2189
Refer to: A07926
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
Description:
Sets the delay time to evaluate the load monitoring.
p2188[0...n]
Load monitoring torque threshold 2, lower / M_thresh 2 lower
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Nm]
20000000.00 [Nm]
0.00 [Nm]
p2189[0...n]
Load monitoring torque threshold 3, upper / M_thresh 3 upper
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Nm]
20000000.00 [Nm]
10000000.00 [Nm]
p2190[0...n]
Load monitoring torque threshold 3, lower / M_thresh 3 lower
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Nm]
20000000.00 [Nm]
0.00 [Nm]
p2192[0...n]
Load monitoring delay time / Load monit t_del
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [s]
65.00 [s]
10.00 [s]