Parameters
List of Parameters
1-180
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the status word of the speed controller.
Description:
Displays the current controller status word.
Description:
Sets the time constant for the speed setpoint filter 1 (PT1).
Description:
Displays the speed setpoint after setpoint limiting for the P component of the speed controller.
For V/f operation, the value that is displayed is of no relevance.
Dependency:
Refer to: r1439
Note:
In the standard state (the reference model is deactivated), r1438 = r1439.
r1407.0...15
CO/BO: Status word speed controller / ZSW n_ctrl
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
V/f control active
Yes
No
-
01
Encoderless operation active
Yes
No
-
02
Torque control active
Yes
No
6030,
6060,
8010
03
Speed control active
Yes
No
6040
05
Speed controller I component frozen
Yes
No
6040
06
Speed controller I component set
Yes
No
6040
07
Torque limit reached
Yes
No
6060
08
Upper torque limit active
Yes
No
6060
09
Lower torque limit active
Yes
No
6060
10
Droop enabled
Yes
No
6030
11
Speed setpoint limited
Yes
No
6030
12
Ramp-function generator set
Yes
No
-
13
Encoderless operation due to a fault
Yes
No
-
15
Torque limit reached (without pre-control)
Yes
No
6060
r1408.0...12
CO/BO: Status word current controller / ZSW I_ctrl
Access level:
4
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Current ctrl act
Active
Not active
-
01
Id control, I component limiting
Active
Not active
6714
03
Voltage limiting
Active
Not active
6714
10
Speed adaptation, limiting
Active
Not active
-
12
Motor stalled
Yes
No
6719,
8018
p1416[0...n]
Speed setpoint filter 1 time constant / n_set_filt 1 T
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [ms]
5000.00 [ms]
0.00 [ms]
r1438
CO: Speed controller, speed setpoint / n_ctrl n_set
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[rpm]
Scaling:
p2000
Data set:
-