Parameters
List of Parameters
1-170
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the open and closed loop control mode of a drive.
Value:
0:
V/f control with linear characteristic
1:
V/f control with linear characteristic and FCC
2:
V/f control with parabolic characteristic
3:
V/f control with parameterizable characteristic
4:
V/f control with linear characteristic and ECO
5:
V/f control for drives requiring a precise freq. (e.g. textiles)
6:
V/f control for drives requiring a precise frequency and FCC
7:
V/f control for a parabolic characteristic and ECO
19:
V/f control with independent voltage setpoint
20:
Speed control (encoderless)
22:
Torque control (encoderless)
Dependency:
Only operation with V/f characteristic is possible if the rated motor speed is not entered (p0311).
Operation with a V/f characteristic is not supported for 1LE4 synchronous motors.
Refer to: p0300, p0311, p1501
Notice:
Active slip compensation is required in the V/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for
the ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note:
Only by selecting closed-loop speed control (p1300 = 20) is it possible to change over in opertaion to closed-loop
torque control (p1501). At the changeover, the setting of p1300 does not change. In this case, the actual state is
displayed in r1407, bit 2 and bit 3.
For the open-loop control modes p1300 = 5 and 6 (textile sector), slip compensation p1335, resonance damping
p1338, and the Imax frequency controller are switched off internally so that the output frequency can be set pre-
cisely. The Imax voltage controller remains active.
During operation (the pulses enabled) the open-loop/closed-loop control mode cannot be changed by changing
over drive data sets.
p1300[0...n]
Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0 22
0