List of Parameters
Parameters
1-137
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the signal source for the speed limit of the positive direction.
Description:
Sets the speed limit for the negative direction.
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description:
Displays the effective negative speed limit.
Dependency:
Refer to: p1082, p1086, p1088
Description:
Sets the signal source for the speed/velocity limit of the negative direction.
Description:
Sets skip speed 1.
Dependency:
Refer to: p1092, p1093, p1094, p1101
Note:
The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
Description:
Sets skip speed 2.
Dependency:
Refer to: p1091, p1093, p1094, p1101
p1085[0...n]
CI: Speed limit in positive direction of rotation / n_limit pos
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 1083[0]
p1086[0...n]
CO: Speed limit in negative direction of rotation / n_limit neg
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
-210000.000 [rpm]
0.000 [rpm]
-210000.000 [rpm]
r1087
CO: Speed limit negative effective / n_limit neg eff
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[rpm]
Scaling:
p2000
Data set:
-
p1088[0...n]
CI: Speed limit in negative direction of rotation / n_limit neg
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 1086[0]
p1091[0...n]
Skip speed 1 / n_skip 1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1092[0...n]
Skip speed 2 / n_skip 2
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Data set:
DDS, p0180
Min Max Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]