List of Parameters
Parameters
1-233
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the interface mode of the PROFIdrive control words and status words.
When selecting a telegram via p0922 (p2079), this parameter influences the device-specific assignment of the bits
in the control and status words.
Value:
0:
SINAMICS
2:
VIK-NAMUR
Dependency:
Refer to: p0922, p2079
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
- For p0922 (p2079) = 1, 350 ... 999, p2038 is automatically set to 0.
- For p0922 (p2079) = 20, p2038 is automatically set to 2.
It is not then possible to change p2038.
Description:
The serial interface for the debug monitor is COM1 (commissioning interface, RS232) or COM2 (fieldbus interface,
RS485).
Value = 0: Deactivated
Value = 1: COM1, commissioning protocol is deactivated
Value = 2: COM2, field bus is deactivated
Value = 3: Reserved
Note:
Value = 2 is only possible for Control Units with RS485 as a field bus interface.
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, an appropriate message is output.
Dependency:
Refer to: F01910
Note:
0: The monitoring is deactivated.
p2038
PROFIdrive STW/ZSW interface mode / PD STW/ZSW IF mode
CU230P-2 DP
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 2 0
p2039
Select debug monitor interface / Sel. debug monitor
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 3 0
p2040
Fieldbus interface monitoring time / Fieldbus t_monit
CU230P-2 HVAC
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 [ms]
65535000 [ms]
100 [ms]