Parameters
List of Parameters
1-300
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the Control Unit temperature.
An appropriate message is output when 87 °C is exceeded.
Index:
[0] = Control Unit temperature actual
[1] = Control Unit temperature maximum
Dependency:
Refer to: A01009
Note:
The value of -200 indicates that there is no measuring signal.
For r3960[0]: Displays the currently measured Control Unit temperature.
For r3960[1]: Displays the highest measured Control Unit temperature. This value is saved on the module in a non-
volatile fashion.
Description:
Displays the device status.
Bit 0: SW reset active
Bit 1: The writing of parameters is disabled, as parameters are being saved.
Bit 2: The writing of parameters is disabled, as a macro is running.
Description:
Displays the counter reading for modified BICO interconnections on this device.
The counter is incremented by one for each modified BICO interconnection.
Description:
Setting to acknowledge all active faults of a drive object.
Note:
Parameter should be set from 0 to 1 to acknowledge.
After acknowledgement, the parameter is automatically reset to 0.
r3960[0...1]
Control Unit temperature / CU temperature
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[°C]
Scaling:
TEMP
Data set:
-
r3974
Device status word / Device status word
Access level:
1
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
SW reset active
active
inactive
-
01
Writing of parameters disabled as parame-
ter save in progress
active
inactive
-
02
Writing of parameters disabled as macro in
progress
active
inactive
-
r3978
BICO CounterDevice / BICO CounterDevice
Access level:
4
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
p3981
Faults, acknowledge drive object / Faults ackn DO
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0
Summary of Contents for CU230P-2 CAN
Page 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Page 2: ......
Page 667: ......