List of Parameters
Parameters
1-189
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the source for the torque setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
No main setpoint
2:
Analog setpoint
6:
Fieldbus
7:
Analog setpoint 2
20:
Analog se no main setpoint
22:
Analog se analog setpoint
26:
Analog se fieldbus
27:
Analog se analog setpoint 2
60:
Fi no main setpoint
62:
Fi analog setpoint
66:
Ffieldbus
67:
Fi analog setpoint 2
70:
Analog setpoint 2 + no main setpoint
72:
Analog setpoint 2 + analog setpoint
76:
Analog setpoint 2 + fieldbus
77:
Analog setpoint 2 + analog setpoint 2
Dependency:
When changing this parameter, the following settings are influenced:
Refer to: p1503, p1511
Note:
With PROFIBUS / PROFINET Control Units, p0922 = 999 must be set so that the command and setpoint sources
can be changed.
Description:
Sets the signal source for toggling between speed and torque control.
Dependency:
The input connectors to enter the torque are provided using p1511, p1512 and p1513.
Refer to: p1300
Caution:
If the closed-loop torque control is not activated (p1300) and a change is made to closed-loop torque control
(p1501), OFF1 (p0840) does not have its own braking response but pulse suppression when standstill is detected
(p1226, p1227).
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
0 signal: Closed-loop speed control
1 signal: Closed-loop torque control
p1500[0...n]
Torque setpoint selection / M_set sel
CU230P-2 HVAC
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
0 77
2
p1501[0...n]
BI: Change over between closed-loop speed/torque control / Changeov n/M_ctrl
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0