Parameters
List of Parameters
1-132
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the signal source for the setting value for the motorized potentiometer.
Dependency:
Refer to: p1043
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator.
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from zero up to the speed/velocity limit (p1082) within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1048, p1082
Note:
When the initial rounding-off is activated (p1030.2) the ramp-up time is correspondingly extended.
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer.
The setpoint is changed from the speed/velocity limit (p1082) to zero within this time (if no initial rounding-off has
been activated).
Dependency:
Refer to: p1030, p1047, p1082
Note:
The deceleration time is extended corresponding to the activated initial rounding-off (p1030.2).
Description:
Sets the effective setpoint after the internal motorized potentiometer ramp-function generator.
This setpoint is the output value of the motorized potentiometer and must be appropriately interconnected onwards
(e.g. with the main setpoint).
Dependency:
Refer to: p1070
Note:
For "With ramp-function generator", after an OFF1, OFF2, OFF3 or for a 0 signal via BI: p0852 (inhibit operation,
cancel pulses) the ramp-function generator output (r1050) is set to the starting value (configuration via p1030.0).
p1044[0...n]
CI: Motorized potentiometer setting value / Mop set val
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
r1045
CO: Mot. potentiometer speed setp. in front of ramp-fct. gen. / Mop n_set bef RFG
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[rpm]
Scaling:
p2000
Data set:
-
p1047[0...n]
Motorized potentiometer ramp-up time / Mop ramp-up time
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 [s]
1000.000 [s]
10.000 [s]
p1048[0...n]
Motorized potentiometer ramp-down time / Mop ramp-down time
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 [s]
1000.000 [s]
10.000 [s]
r1050
CO: Motor. potentiometer setpoint after the ramp-function generator /
Mop setp after RFG
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[rpm]
Scaling:
p2000
Data set:
-