Parameters
List of Parameters
1-268
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the second status word for monitoring functions.
Note:
Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 12:
If the fault condition is removed, bit 12 is reset to 0. This is also the case even if the alarm message is still present.
Description:
Displays the third status word for monitoring functions.
Note:
Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit will never be reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
Description:
Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
r2198.0...13
CO/BO: Status word monitoring 2 / ZSW monitor 2
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
|n_act| <= speed threshold value 5
Yes
No
8021
01
|n_act| > speed threshold value 5
Yes
No
8021
02
|n_act| <= speed threshold value 6
Yes
No
8021
03
|n_act| > speed threshold value 6
Yes
No
8021
04
|n_set| < p2161
Yes
No
8011
05
n_set > 0
Yes
No
8011
06
Motor locked
Yes
No
8012
07
Motor stalled
Yes
No
8012
08
|I_act| < I_threshold value p2170
Yes
No
8020
09
|M_act| > torque threshold value 1 and
n_set reached
Yes
No
8021
10
|M_set| < torque threshold value 1
Yes
No
8012
11
Load monitoring signals an alarm
Yes
No
8013
12
Load monitoring signals a fault condition
Yes
No
8013
13
|M_act| > torque threshold value 1
Yes
No
8021
r2199.0...11
CO/BO: Status word monitoring 3 / ZSW monitor 3
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
|n_act| < speed threshold value 3
Yes
No
8010
01
f or n comparison value reached or
exceeded
Yes
No
8010
04
Speed setp - act val deviation in tolerance
t_on
Yes
No
8011
05
Ramp-up/ramp-down completed
Yes
No
8011
11
Torque utilization < torque threshold value 2 Yes
No
8012
p2200[0...n]
BI: Technology controller enable / Tec_ctrl enable
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0