Parameters
List of Parameters
1-398
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Display parameter for output pulse Q of instance PDE 3 of the closing delay device.
Description:
Setting parameter for the run-time group in which instance PDE 3 of the closing delay device is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance PDE 3 within the run-time group set in p20342.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source for the input pulse I of instance PDF 2 of the breaking delay device.
Description:
Setting parameter for pulse extension time T in milliseconds of instance PDF 2 of the breaking delay device.
Description:
Display parameter for output pulse Q of instance PDF 2 of the breaking delay device.
Description:
Setting parameter for the run-time group in which the instance PDF 2 of the breaking delay device is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
r20341
BO: PDE 3 output Q / PDE 3 output Q
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
p20342
PDE 3 run-time group / PDE 3 RTG
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
5 9999
9999
p20343
PDE 3 run sequence / PDE 3 RunSeq
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 32000
900
p20344
BI: PDF 2 input pulse I / PDF 2 inp_pulse I
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
- - 0
p20345
PDF 2 pulse extension time in ms / PDF 2 t_ext ms
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 60000.00
0.00
r20346
BO: PDF 2 output Q / PDF 2 output Q
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
p20347
PDF 2 run-time group / PDF 2 RTG
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
5 9999
9999