List of Parameters
Parameters
1-291
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays the status word for the "Hibernation" function.
Dependency:
Refer to: p2398
Refer to: A07325
Description:
Sets a fixed percentage.
Dependency:
Refer to: p2901, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the main setpoint)
Description:
Sets a fixed percentage.
Dependency:
Refer to: p2900, p2930
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
r2399.0...8
CO/BO: Hibernation status word / Hib ZSW
Access level:
3
Calculated:
-
Data type:
Unsigned32
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Hibernation enabled (p2398 <> 0)
Yes
No
-
01
Hibernation active
Yes
No
-
02
Hibernation delay time active
Yes
No
-
03
Hibernation boost active
Yes
No
-
04
Hibernation motor powered down
Yes
No
-
05
Hibernation motor powered down cyclic
restart active
Yes
No
-
06
Hibernation motor restarts
Yes
No
-
07
Hibernation supplies total setpoint for ramp-
function generator
Yes
No
-
08
Hibernation bypasses ramp-fct generator in
setpoint channel
Yes
No
-
p2900[0...n]
CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-10000.00 [%]
10000.00 [%]
0.00 [%]
p2901[0...n]
CO: Fixed value 2 [%] / Fixed value 2 [%]
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
DDS, p0180
Min Max Factory
setting
-10000.00 [%]
10000.00 [%]
0.00 [%]