Parameters
List of Parameters
1-272
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Selects the method that can be used to select the fixed setpoints.
Value:
1:
Fixed value selection direct
2:
Fixed value selection binary
Description:
Sets the signal source to select the fixed value of the technology controller.
Dependency:
Refer to: p2221, p2222, p2223
Description:
Sets the signal source to select the fixed value of the technology controller.
Dependency:
Refer to: p2220, p2222, p2223
Description:
Sets the signal source to select the fixed value of the technology controller.
Dependency:
Refer to: p2220, p2221, p2223
Description:
Sets the signal source to select the fixed value of the technology controller.
Dependency:
Refer to: p2220, p2221, p2222
Description:
Displays the selected and effective fixed value of the technology controller.
Dependency:
Refer to: r2229
p2216[0...n]
Technology controller fixed value selection method / Tec_ctr FixVal sel
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
1 2 1
p2220[0...n]
BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 722.3
p2221[0...n]
BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 722.4
p2222[0...n]
BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 722.5
p2223[0...n]
BI: Technology controller fixed value selection bit 3 / Tec_ctrl sel bit 3
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
r2224
CO: Technology controller, fixed value effective / Tec_ctr FixVal eff
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-