Parameters
List of Parameters
1-174
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the frequency of the fourth point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
The following applies to the frequency values: p1320 <= p1322 <= p1324 <= p1326. Otherwise, a standard charac-
teristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1327
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327. For output fre-
quencies above p1326, the characteristic is extrapolated with the gradient between the characteristic points
p1324/p1325 and p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/f characteristic.
Description:
The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the fourth point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1326
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable V/f characteristic.
Description:
Sets the signal source for the voltage setpoint for V/f control with an independent voltage setpoint (p1300 = 19).
Dependency:
Selects the V/f control with independent voltage setpoint via p1300 = 19.
Refer to: p1300
Description:
Sets the starting frequency at which FCC (Flux Current Control) is activated.
Dependency:
The correct operating mode must be set (p1300 = 1, 6).
Warning:
An excessively low value can result in instability.
Note:
For p1333 = 0 Hz, the FCC starting frequency is automatically set to 6 % of the rated motor frequency.
p1326[0...n]
V/f control programmable characteristic frequency 4 / Vf char f4
Access level:
3
Calculated:
p0340 = 1,3
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Hz]
10000.00 [Hz]
0.00 [Hz]
p1327[0...n]
V/f control programmable characteristic voltage 4 / Vf char U4
Access level:
3
Calculated:
p0340 = 1,3
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.0 [Vrms]
10000.0 [Vrms]
0.0 [Vrms]
p1330[0...n]
CI: V/f control independent voltage setpoint / Vf V_set independ.
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2001
Data set:
CDS, p0170
Min Max Factory
setting
- - 0
p1333[0...n]
V/f control FCC starting frequency / V/f FCC f_start
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]