Parameters
List of Parameters
1-254
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Displays additional information about the active alarm for float values.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2125, r2145, r2146
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description:
Displays the second status word of faults and alarms.
Description:
Displays the system runtime in days when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, p8401
Notice:
The time comprises r2136 (days) and r2109 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description:
Displays the control word of the faults and alarms.
Dependency:
Refer to: p2103, p2104, p2105, p2106, p2107, p2108, p2112, p2116, p2117, p3110, p3111, p3112
r2134[0...63]
Alarm value for float values / Alarm value float
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Unit:
-
Scaling:
-
Data set:
-
r2135.12...15
CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2
Access level:
2
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
12
Fault motor overtemperature
Yes
No
-
13
Fault power unit thermal overload
Yes
No
-
14
Alarm motor overtemperature
Yes
No
-
15
Alarm power unit thermal overload
Yes
No
-
r2136[0...63]
Fault time removed in days / t_flt resolv. days
Access level:
3
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
r2138.7...15
CO/BO: Control word faults/alarms / STW fault/alarm
Access level:
2
Calculated:
-
Data type:
Unsigned16
Unit:
-
Scaling:
-
Data set:
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
07
Acknowledge fault
Yes
No
-
10
External alarm 1 (A07850) effective
Yes
No
-
11
External alarm 2 (A07851) effective
Yes
No
-
12
External alarm 3 (A07852) effective
Yes
No
-
13
External fault 1 (F07860) effective
Yes
No
-
14
External fault 2 (F07861) effective
Yes
No
-
15
External fault 3 (F07862) effective
Yes
No
-
Summary of Contents for CU230P-2 CAN
Page 1: ...s SINAMICS G120 Control Units CU230P 2 Parameter Manual 11 2009 SINAMICS ...
Page 2: ......
Page 667: ......