List of Parameters
Parameters
1-275
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency:
Refer to: r2250
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2248
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
Refer to: p2247
Note:
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
Refer to: r2245
Description:
Sets the mode for using the technology controller output.
Value:
0:
Technology controller as main speed setpoint
1:
Technology controller as supplementary speed setpoint
Dependency:
p2251 = 0, 1 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
Description:
Sets the signal source for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2254, p2255
r2245
CO: Techn. controller mot. potentiometer setpoint before RFG / Tec_ctr mop befRFG
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
p2247[0...n]
Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.0 [s]
1000.0 [s]
10.0 [s]
p2248[0...n]
Techn. controller motorized potentiometer ramp-down time / Tec_ctrMop t_rdown
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.0 [s]
1000.0 [s]
10.0 [s]
r2250
CO: Techn. controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
p2251
Technology controller mode / Tec_ctrl mode
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 1 0
p2253[0...n]
CI: Technology controller setpoint 1 / Tec_ctrl setp 1
Access level:
2
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
CDS, p0170
Min Max Factory
setting
- - 0