Parameters
List of Parameters
1-56
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the stator direct-axis inductance of the synchronous motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Note:
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is ideal for a low cur-
rent.
Description:
Sets the rotor/secondary section leakage inductance of the motor.
The value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910).
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
If the rotor leakage inductance (p0358) for induction motors is changed outside the commissioning phase (p0010 >
0), then the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then
advised to repeat the measurement for the saturation characteristic (p1960).
Description:
Sets the magnetizing inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Caution:
This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2).
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 1st value pair of the characteristic.
Sets the first flux value of the saturation characteristic as a [%] referred to the rated motor flux (100 %).
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
Refer to: p0366
Note:
For induction motors, p0362 = 100 % corresponds to the rated motor flux.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
p0357[0...n]
Motor stator inductance, d axis / Mot L_stator d
Access level:
3
Calculated:
p0340 = 1,2
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
0.00000 [mH]
1000.00000 [mH]
0.00000 [mH]
p0358[0...n]
Motor rotor leakage inductance / Mot L_rot leak
Access level:
3
Calculated:
p0340 = 1,2
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
0.00000 [mH]
1000.00000 [mH]
0.00000 [mH]
p0360[0...n]
Motor magnetizing inductance / Mot Lh
Access level:
3
Calculated:
p0340 = 1,2
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
0.00000 [mH]
10000.00000 [mH]
0.00000 [mH]
p0362[0...n]
Saturation characteristic flux 1 / Mot saturat.flux 1
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Data set:
MDS
Min Max Factory
setting
10.0 [%]
300.0 [%]
60.0 [%]