Parameters
List of Parameters
1-316
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the CANopen NMT state that is effective after booting.
Value:
4:
Stopped
5:
Operational
127:
Pre-operational
Dependency:
Refer to: p8685
Note:
Booting in the NMT state pre-operational corresponds to the CANopen standard
Description:
Sets and displays the CANopen NMT state.
Value:
0:
Initializing
4:
Stopped
5:
Operational
127:
Pre-operational
128:
Reset node
129:
Reset Communication
Note:
The value 0 (initialization) is only displayed and cannot be set.
Description:
Sets the communication parameters for CANopen Receive Process Data Object 1 (RPDO 1).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note:
Corresponds to the CANopen object 1400 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
Description:
Sets the communication parameters for CANopen Receive Process Data Object 2 (RPDO 2).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Note:
Corresponds to the CANopen object 1401 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1, FE and FF can be set.
PDO: Process Data Object
p8684
CAN NMT state after booting / NMT state boot
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Data set:
-
Min Max Factory
setting
4 127
127
p8685
CAN NMT states / NMT states
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(1), U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0 129
127
p8700[0...1]
CAN Receive PDO 1 / Receive PDO 1
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
8000 06DF hex
8000 06DF hex
p8701[0...1]
CAN Receive PDO 2 / Receive PDO 2
CU230P-2 CAN
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(3), T
Scaling:
-
Data set:
-
Min Max Factory
setting
0000 hex
8000 06DF hex
8000 06DF hex