SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
Description:
Sets the signal source for control word 1 bit 4 (operating condition/disable ramp-function generator).
Dependency:
Refer to: r0054, p1141, p1142
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Bit 4 = 0: Inhibit ramp-function generator (the ramp-function generator output is set to zero)
Bit 4 = 1: Operating condition (the ramp-function generator can be enabled)
Description:
Sets the signal source for control word 1 bit 4 (operating condition/disable ramp-function generator).
Dependency:
Refer to: r0054, p1141, p1142
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Bit 4 = 0: Inhibit ramp-function generator (the ramp-function generator output is set to zero)
Bit 4 = 1: Operating condition (the ramp-function generator can be enabled)
Description:
Sets the signal source for control word 1 bit 5 (continue ramp-function generator/freeze ramp-function generator).
Dependency:
Refer to: r0054, p1140, p1142
Notice:
The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
Note:
Bit 5 = 0: Freeze ramp-function generator
Bit 5 = 1: Continue ramp-function generator
p1137[0...n]
OFF3 final rounding-off time / RFG OFF3 t_end_del
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
DDS, p0180
Min Max Factory
setting
0.000 [s]
30.000 [s]
0.000 [s]
p1140[0...n]
BI: Ramp-function generator enable / RFG enable
CU230P-2 CAN
CU230P-2 HVAC
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 1
p1140[0...n]
BI: Ramp-function generator enable / RFG enable
CU230P-2 DP
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 2090.4
p1141[0...n]
BI: Continue ramp-function generator / Continue RFG
CU230P-2 CAN
CU230P-2 HVAC
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Data set:
CDS, p0170
Min Max Factory
setting
- - 1