List of Parameters
Parameters
1-339
© Siemens AG 2009 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 11/2009
Description:
Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11091, p11092) of the free technol-
ogy controller 0.
Dependency:
Refer to: p11091, p11092
Note:
The ramp-up/ramp-down times are referred to 100%.
Description:
Display and connector output for the output signal of the free technology controller 0.
Description:
Sets the signal source for the maximum limit of the free technology controller 0.
Dependency:
Refer to: p11091
Description:
Sets the signal source for the minimum limit of the free technology controller 0.
Dependency:
Refer to: p11092
Description:
Sets the signal source for the limit offset of the free technology controller 0.
p11093
Free tec_ctrl 0 limit ramp-up/ramp-down time / Ftec0 lim r-u/r-dn
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Data set:
-
Min Max Factory
setting
0.00 [s]
100.00 [s]
1.00 [s]
r11094
CO: Free tec_ctrl 0 output signal / Ftec0 out_sig
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Unit:
[%]
Scaling:
PERCENT
Data set:
-
p11097
CI: Free tec_ctrl 0 limit maximum signal source / Ftec0 lim max s_s
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 11091[0]
p11098
CI: Free tec_ctrl 0 limit minimum signal source / Ftec0 lim min s_s
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 11092[0]
p11099
CI: Free tec_ctrl 0 limit offset signal source / Ftec0 lim offs
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Data set:
-
Min Max Factory
setting
- - 0